Electromagnetic Flowmeter

LD Series Electromagnetic Flowmeter
LD Series Electromagnetic Flowmeter
Category:Electromagnetic Flowmeter
Description:Electromagnetic Flowmeter
  • Overview

  • Specifications

  • Dimensions

  • Measuring ranges

Overview


The LD series electromagnetic flowmeter is used to measure the volume flow of conductive fluid in a closed pipeline. It is widely used in the measurement and control of production process flow in petrochemical, iron and steel metallurgy, water supply and drainage, water conservancy irrigation, water treatment, total environmental sewage control, papermaking, medicine, food and other departments; suitable for the measurement of conductive liquids.

Specifications


Depending on selected device configuration

General information

Product type

Flowmeter

Product family name

LD

Product positioning

For liguids applications

Measurement principles

Electromagnetic

Measured media

Liquids

Communication

Digital outputs

HART® 485

Discrete outputs 

Frequency, Limit switches, Pulse

Analogue outputs 

4…20 mA

Materials

Liner

Polyuretane (PUR) Perfluoroalkoxy alkane (PFA) Nitrile Rubber (NBR)

Electrodes

316L,Hb,Hc,Ti,Ta,Pt

Process connection

304SS  316SS Cast iron

Operating conditions

Process temperature

-30…+180°C

Process connections

Flange connections

DN10…1200

Thread  connections

G1...G2

Dimensions


1640782665168952.jpg


Measuring ranges


Medium conductivity:≥5μ s/cm ,softener water≥20μ s/cm
Accuracy:±1%RS-±1.5%RS
Velocity of flow:0.3m/s-5m/s
Working temp.:compact≤100°C
Working pressure: 4.0MPa(base on diameter)
Protection class:IP65,IP67,IP68(Remote)

1640783596210208.jpg